The SPR-228 is a high-performance multifunction electrical tester designed for comprehensive electrical testing in industrial, commercial, and residential environments. It supports six core functions: insulation resistance testing, earth resistance measurement, low ohm resistance testing, voltage and frequency measurement, loop impedance testing, and RCD (Residual Current Device) testing. With built-in data logging, Bluetooth connectivity, and a large color TFT display, the SPR-228 offers advanced diagnostics and reporting capabilities.
This device meets international safety standards (IEC 61010, CAT III 600V), ensuring safe operation in demanding environments. It is ideal for electricians, maintenance engineers, and electrical contractors who require accurate and reliable test results for system commissioning, periodic inspections, and preventive maintenance.
- Six-in-One Testing: Insulation resistance, earth resistance, low ohm resistance, loop impedance, RCD testing, and voltage/frequency measurement
- Data Logging & Storage: Built-in memory with FAT32 file system for storing test records; supports export to PC or mobile devices
- Large Color Display: 3.5" TFT LCD with high-resolution graphics for clear visualization of waveforms and data
- RCD Testing Modes: Supports general (G-type) and selective (S-type) RCDs with multiple trip current options and ramp testing
- Loop Impedance Testing: Measures prospective short-circuit current (PSC) and earth fault current (PFC)
- Auto Test Sequences: Simplifies complex testing procedures with automated routines for continuity, insulation, and loop tests
- Battery-Powered Operation: Operates on 8 x AA batteries (alkaline or NiMH); up to 15 hours of continuous use
- Safety Certified: Complies with IEC/EN 61010; double insulation, IP65 rating, CAT III 600V overvoltage category
- Bluetooth Connectivity (optional): Enables wireless data transfer to smartphones or tablets for real-time analysis and reporting
| Parameter | Details |
|---|---|
| Functions Supported | Insulation Resistance, Earth Resistance, Low Ohm, Loop Impedance, Voltage/Frequency, RCD Testing |
| Insulation Resistance Range | 0.01MΩ – 9999MΩ; Test voltages: 50V, 100V, 250V, 500V, 1000V |
| Earth Resistance Range | 0.01Ω – 1999Ω; Test current: > 200mA |
| Low Ohm Resistance Range | 0.001Ω – 19.999Ω; Resolution: 1mΩ; Accuracy: ±(1% + 1mΩ) |
| Loop Impedance Range | 0.01Ω – 1999Ω; Prospective Fault Current (PFC): up to 25kA |
| Voltage Measurement (AC) | 80V – 500V; Accuracy: ±(2% + 2 digits); Frequency range: 45Hz – 65Hz |
| Frequency Measurement | 45Hz – 65Hz; Accuracy: ±2Hz |
| RCD Testing | Trip currents: 10mA, 30mA, 100mA, 300mA, 500mA, 650mA, 1A; Delay types: G/S |
| Test Methods | Auto, Ramp, Half-wave, Full-wave |
| Polarity Detection | Yes; indicates reversed connections |
| Display | 3.5" TFT LCD (320x240 pixels) |
| Data Logging | File-based storage; up to 310MB free space; supports time-stamped logs |
| Power Supply | 8 x 1.5V AA alkaline or 8 x 1.2V NiMH rechargeable batteries |
| Battery Life | Up to 15 hours (typical usage) |
| Auto Power Off | Adjustable (disable, 1 min, 10 min, 20 min) |
| Auto Screen Off | Adjustable (disable, 1 min, 3 min, 5 min) |
| Overvoltage Protection | CAT III 600V |
| Safety Rating | Double Insulation, IP65 |
| Operating Temperature | 0°C to 45°C |
| Storage Temperature | -10°C to 60°C |
| Humidity (Operating) | <95% RH (10°C–30°C non-condensing), <75% RH (30°C–40°C) |
| Dimensions | 24.2cm x 10.5cm x 14.5cm (L x W x H) |
| Weight | 1.56kg |
| Approvals | CE Marked |