The Sonel MPI-502F is a compact multifunction meter for checking electrical installations. It measures fault loop impedance (0.13 Ω to 1999 Ω), tests AC and A type RCDs, checks protective conductor continuity with ±200 mA, and measures voltage and frequency. With IP67, CAT IV 300 V and Bluetooth, it suits household and industrial safety inspections. Supplied with the WS-03 adapter, test leads, carrying case, batteries and factory calibration certificate.
• Fault loop impedance ZL-PE, ZL-N, ZL-L with R and X indication
• 15 mA loop measurement without tripping the RCD
• Tests AC and A type RCDs: general, short-delay and selective
• Auto RCD mode with IA and tA measured during one tripping
• Continuity of protective conductors with ±200 mA (EN 61557-4)
• Low-current resistance measurement with sound signaling
• Voltage (0 to 500 V) and frequency measurement
• IP67 housing, CAT IV 300 V, Bluetooth and 990-cell memory
| Loop Impedance Range | 0.13 Ω to 1999 Ω (ZL-PE, ZL-N, ZL-L) |
| Loop Accuracy | ±(5% m.v. + 3 digits) |
| Loop Operating Voltage | 180 to 460 V, 45 to 65 Hz |
| Max Test Current | 7.6 A (230 V), 13.3 A (400 V) |
| RCD Rated Currents | 10, 15, 30, 100, 300, 500 mA |
| RCD Trip Time tA | 0 to 300 ms (general/short-delay), 0 to 500 ms (selective) |
| RCD Trip Current IA | 3.0 to 500 mA (AC), 3.5 to 420 mA (type A) |
| Continuity (±200 mA) | 0.12 Ω to 400 Ω, ±(2% m.v. + 3 digits) |
| Voltage Measurement | 0 to 500 V |
| Memory | 990 cells, 10,000 records |
| Protection / Category | IP67, CAT IV 300 V (CAT III 600 V) |
| Weight | approx. 0.8 kg |