The Sonel MPI-506 is a compact multifunctional installations meter for checking electrical safety in homes and industrial facilities. It measures fault loop impedance (0.13 Ω to 1999 Ω), tests AC and A type RCDs, measures insulation resistance at 100/250/500 V, checks protective conductor continuity with ±200 mA and indicates phase sequence. IP67 and Bluetooth. Includes WS-03 adapter, test leads, probes, clips, carrying case, batteries and calibration certificate.
• Fault loop impedance ZL-PE, ZL-N, ZL-L with R and X indication
• Loop test with 15 mA current without tripping the RCD
• Tests general, short-delay and selective AC and A type RCDs
• Auto RCD mode and IA/tA measurement during one RCD tripping
• Insulation resistance at 100 V, 250 V and 500 V
• Continuity of protective conductors with ±200 mA and test lead autocalibration
• Phase sequence indication and voltage/frequency measurement
• IP67 housing, CAT IV 300 V, 990-cell memory with Bluetooth transfer
| Loop Impedance Range | 0.13 Ω…1999 Ω (±5% m.v. + 3 digits) |
| Max Loop Test Current | 7.6 A (230 V), 13.3 A (400 V) |
| RCD Types / Ratings | AC, A; 10, 15, 30, 100, 300, 500 mA |
| RCD Trip Time tA | 0…300 ms (general), 0…500 ms (selective) |
| Insulation Test Voltages | 100 V, 250 V, 500 V |
| Insulation Range (500 V) | 500 kΩ…599.9 MΩ |
| Continuity (±200 mA) | 0.12 Ω…400 Ω (±2% m.v. + 3 digits) |
| Measuring Category | IV 300 V (III 600 V) |
| Ingress Protection | IP67 |
| Memory | 990 cells, 10,000 records |
| Dimensions | 220 × 102 × 61 mm |
| Weight | approx. 0.8 kg |